TEMPORARY ERECTION

BRACING SYSTEM (IN ACCORDANCE TO UKTFA GUIDANCE)


  I-Joists are unstable until laterally braced!
  These instructions are offered as general recommendations and in some instances other and/or
    additional precautions may be necessary.
  Erection and bracing procedures and the workers' safety are the responsibility of the builder.
  Do not allow workers or construction loads on unbraced I-Joists!
  These details may also be used with timber frame construction.

Longitudinal Bracing
1. 
Use at least 19 x 89mm bracing members nailed to each I-Joist with two 3.35 x 65mm nails.  Use
     long pieces, not short lengths.  Lap the ends to keep a continuous line of bracing.
2.  Braces are required at the ends of each I-Joist and at interior supports of continuous I-Joists.  Keep
     the braces parallel and a maximum of 2.4m apart.  Longitudinal braces must be tied to a diagonally
     braced and blocked system at one end of each I-Joist run or joist bay.
3.  Additional braces and blocking systems may be required e.g. around stairwell openings.

Diagonal Bracing
1. 
Use at least 19 x 89mm bracing members nailed to each I-Joist with two 3.35 x 65mm nails.
     Use continuous pieces.
2.  Diagonal braces must be installed at one end of each I-Joist run or I-Joist bay.  In long joist runs
     install additional diagonal bracing systems at not more than 10m spacing.
3.  Diagonal bracing must be fixed to a minimum of 3 I-Joists to cover a distance of at least 1.2m.

Temporary Stability Blocking
1. 
Temporary stability blocking should be a minimum cross section of 38 x 125mm solid timber.
     Fasten with at least two 3.35 x 65mm nails at each end.  Alternatively the required permanent
     blocking may be fitted e.g. for cantilever joists (see Finnforest Installation details).
2.  Blocking should be cut accurately to length with square ends to maintain Finnjoist centres.
3.  Blocking must be fixed between at least 3 I-Joists or to cover a minimum distance of 1.2m.
4.  Blocking must be installed at the supports of I-Joists including interior supports of continuous I-Joists
     where the overall length of the Finnjoist exceeds 6.0m.
5.  Blocking must be installed at one end of each I-Joist run or I-Joist bay.  In long joist runs install
     additional blocking systems (temporary stability blocking and diagonal bracing) at not more than
    10m spacing.

Construction Loads
Please contact Finnforest Technical Support for guidance on 01205 883 835.